Brunel University
Supported for HurleyPalmerFlatt the natural ventilation strategy, predicted the Heating & Cooling Loads of a 7,500m² educational building with auditorium and central atrium creating the IES DTM (Dynamic Thermal Model) and participating in the CFD (Computational Fluid Dynamic) modelling team work.
Also composed for HurleyPalmerFlatt the overheating study for BB101 (Compliance for ventilation and indoor air quality in British schools) for the mixed mode ventilation.
Also composed for HurleyPalmerFlatt the overheating study for BB101 (Compliance for ventilation and indoor air quality in British schools) for the mixed mode ventilation.
Overheating Analysis Model
BB101 – Compliance for ventilation and indoor air quality in British schools.
Overheating Analysis Requirements BB10
What the IES model reviewed:
- The annual school overheating hrs on a test reference weather file
- If No of hours that internal temperature exceeds 28 C is < 120 hrs
- If the difference between internal and external temperature is <5
- If the internal temperature is <32 C
Window Opening Regime
Top floor office windows were reviewed with CFD modelling for air circulation competency.